Inputs |
System | 3 Phase 4 Wire |
Voltage(V) |
Norminal voltage AC | 3×230/400VAC |
Voltage rage | -30% to +30% of nominal voltage |
Input Withstand Capability | Meets IEEE C37.90.1 (Surge Withstand Capability) |
Current(A) |
Imin | 0.25A |
Itr | 0.5A |
Iref(Ib) | 5A |
Ist | 10mA |
Withstand | 500A for 0.01 Second |
Accuracy |
kWh | Better than Class 1 per EN 62053-21 & BS 8431 |
Kvarh | Better than Class 2 per EN 62053-23 & BS 8431 |
kW & kVA | Better than Class 0.5 IEC 60688 |
kvar | Better than Class 0.5 IEC 60688 |
Amps & Volts | Class 0.2 IEC 60688 (0.01In – 1.2In or 0.1Un – 1.2Un) |
PF | ±0.2° (0.05In – 1.2In and 0.2Un – 1.2Un) |
Neutral Current | Class 0.5 IEC 60688 (0.05In – 1.2In) |
General data |
Power supply | (65 to 275) Volts AC. Universal AC/DC Supply |
Frequency(Hz) | 50 / 60Hz |
Frequency range | ±5% |
Temperature(℃) | Operating -10 to +65 Storage -25 to +70 |
Humidity | 75% RH Non-Condensing |
Environment | IP54 standard, IP65 optional |
Faceplate Rating | NEMA12 (Water Resistant) |
Primary current | 50、60、75、100、125、150、160、200、250、300、400、500、600、750、800、1000、1200、1250、1500、2000、2400、2500、3000、4000、5000、6000、7500 |
Display |
Type | 6+1 LCD display |
Form | 10×5mm high digits |
Scaling | Direct reading. User programmable CT |
Backlight | White, others to order. |
Pulse output |
Pulse wide | 80ms±20ms |
Pulse frequency(imp/kWh) | 1600 |
Type | N/O Volt free contact. Optically isolated BiFET |
Isolation | 4kV 50Hz 1minute |
Contacts | current : 27mA DC Max voltage : 5-27V DC |
Connection area,main terminals |
Flexible 1×mm2 | 0-2.5 |
Solide 1×mm2 | 0-2.5 |
LED |
Pulse wide | 80ms±20ms |
Pulse frequency(imp/kWh) | 1600 |
Mechanical |
Dimensions(mm) | Width: 96 Height: 96 Depth: 55 |
Standard compliance | IEC 62052-11 IEC62053-21 EN 50470-1 EN 50470-3 |