l High Sample Rate: the synchronous sampling rate reach as high as about 6kHz.
l Real-time Operation: within 2mS after very cycle, the meter can liquidate all the RMS value, power and other parameters to meet the requirement of protected-level operation.
l High Communication Rate:RS485 :1200 bps-115.2kbps.
l Flexible communication protocol: each meter supports several usual protocol addresses or specially designed protocol addresses .
l Analysis of Higher Harmonic : harmonic measurement:2nd-60th, the harmonic algorithm accuracy: 0.2%;the accuracy of the whole meter :0.5%
l Abundant Statistical Data: the meter can calculate the demand and the maximum or minimum of the voltage ,current and power with the RTC time label to choose.
l High Reliability: the meter has passed 4 level EMC test and can operate with full voltage under the perceptual power-fail intelligent storage system.
1. Voltage Inputs
• 20-280 Volts Line To Neutral, 20-480 Volts Line to Line
• Universal Voltage Input
• Input Withstand Capability – Meets IEEE C37.90.1 (Surge Withstand Capability)
• Programmable Voltage Range to Any PT ratio
• Supports: 3 phase 3 or 4 wires, 400/230V, 110/63V,208/120V
• Burden: 0.36VA per phase Max at 600V, 0.014VA at 120 Volts
• Input wire gauge max (AWG 12 / 2.5mmPPP2PPP)
2. Current Inputs
• Class : (0 to 5) A, 5 Amp Nominal
• Fault Current Withstand: 100 Amps for 10 Seconds, 300 Amps for 3 Seconds, 500 Amps for 1 Second.
• Programmable Current to Any CT Ratio
• Burden 0.005VA per phase Max at 11Amps
• 5mA Pickup Current
• Pass through wire gauge dimension: 0.177" / 4.5mm
• Continuous current withstand: 20 amps for screw terminated or pass through current connections
3. Isolation
All Inputs and Outputs are galvanically isolated to 2500 Volts AC.
4. Environmental Rating
Storage: (-25 to +70)° C
Operating: (-10 to +65)° C
Humidity: to 75% RH Non-Condensing
Faceplate Rating: NEMA12 (Water Resistant)
Environment : IP54 standard, IP65 optional
Mounting Gasket Included
5. Sensing Method
• RMS
• Sampling at 120+ Samples per Cycle on all channels measured readings simultaneously
• Harmonic %THD (% of Total Harmonic Distortion)
6. Update Rate
• Watts, VAr and VA-100msec
• All other parameters-1second
7. Power Supply
Option D2:
• (65 to 275) Volts AC and (90 to 380) Volts DC. Universal AC/DC Supply
Option D:
• 18-60VDC Burden: 10VA max.
8. Communication Format
• 2 Com Ports (Back and Face Plate)
• RS485 Port (Through Back Plate)
• 10/100 BaseT Ethernet Modbus TCP (INP10)
• Com Port Baud Rate: (1200 to 115200)
• Com Port Address: 0-247
• 8 Bit, No parity
• Modbus RTU Protocols
9. KYZ Pulse
• Type Form A
• On Resistance: 23-35 Ohm
• Peak Voltage: 350 VDC
• Continuous Load Current: 120 mA
• Peak Load Current: 350mA (10ms)
• Off Stat Leakage Current @ 350VDC: 1 mA
• Opto-Isolation: 3750V (6 0Hz, 1min)
10. Meter Accuracy and Resolution
ITEM | Accuracy | Resolution |
Voltage | 0.20% | 0.1V(PT ratio) |
Current | 0.20% | 1mA(PT ratio) |
Frequency | 0.10% | 0.01Hz |
Power | 0.50% | 1W/Var/VA(PT ratio) |
Power factor | 0.50% | 0.001 |
Energy | 0.50% | 0.1HWh/KVarh/KVAh |
Harmonics | 0.50% | 0.01% |
Unbalance level | 0.50% | 0.10% |
11.Standard compliance
11. IEC 62052-11
IEC62053-21;EN 50470-1;EN 50470-3